Nec Underground Cover: under 4in exterior concrete slab
NEC (NFPA 70) Table 300.5 — minimum burial cover depths for underground wiring installations by location type and wiring method (direct burial cable, rigid metal conduit/IMC, nonmetallic raceway, residential GFCI branch circuit, irrigation at 30 V or less)
| location id | col1 direct burial mm (mm) | col2 rmc imc mm (mm) | col3 nonmetallic raceway mm (mm) | col4 residential gfci mm (mm) | col5 irrigation 30v mm (mm) | location description | nec section | standard |
|---|---|---|---|---|---|---|---|---|
| under 4in exterior concrete slab | 450 | 100 | 100 | 150 | 150 | Under minimum 102 mm (4 in.) thick concrete exterior slab, no vehicular traffic, slab extends 152 mm beyond installation | 300.5 | NEC (NFPA 70) 2017 Table 300.5 |