Nec Underground Cover: general

NEC (NFPA 70) Table 300.5 — minimum burial cover depths for underground wiring installations by location type and wiring method (direct burial cable, rigid metal conduit/IMC, nonmetallic raceway, residential GFCI branch circuit, irrigation at 30 V or less)

Electrical Engineeringlocation id: general1 row
location idcol1 direct burial mm (mm)col2 rmc imc mm (mm)col3 nonmetallic raceway mm (mm)col4 residential gfci mm (mm)col5 irrigation 30v mm (mm)location descriptionnec sectionstandard
general600150450300150All locations not specified below300.5NEC (NFPA 70) 2017 Table 300.5