Nec Underground Cover: residential_driveway to under_streets_highways
NEC (NFPA 70) Table 300.5 — minimum burial cover depths for underground wiring installations by location type and wiring method (direct burial cable, rigid metal conduit/IMC, nonmetallic raceway, residential GFCI branch circuit, irrigation at 30 V or less)
| location id | col1 direct burial mm (mm) | col2 rmc imc mm (mm) | col3 nonmetallic raceway mm (mm) | col4 residential gfci mm (mm) | col5 irrigation 30v mm (mm) | location description | nec section | standard |
|---|---|---|---|---|---|---|---|---|
| residential_driveway | 450 | 450 | 450 | 300 | 450 | One- and two-family dwelling driveways and outdoor parking, dwelling-related purposes only | 300.5 | NEC (NFPA 70) 2017 Table 300.5 |
| under_streets_highways | 600 | 600 | 600 | 600 | 600 | Under streets, highways, roads, alleys, driveways, and parking lots | 300.5 | NEC (NFPA 70) 2017 Table 300.5 |
This is a sample. Search the full nec underground cover dataset and 350+ more by creating a free account and accessing the database.