Nec Underground Cover: general to airport_runway

NEC (NFPA 70) Table 300.5 — minimum burial cover depths for underground wiring installations by location type and wiring method (direct burial cable, rigid metal conduit/IMC, nonmetallic raceway, residential GFCI branch circuit, irrigation at 30 V or less)

Electrical Engineeringlocation_id: general to airport_runway5 rows
location idcol1 direct burial mm (mm)col2 rmc imc mm (mm)col3 nonmetallic raceway mm (mm)col4 residential gfci mm (mm)col5 irrigation 30v mm (mm)location descriptionnec sectionstandard
general600150450300150All locations not specified below300.5NEC (NFPA 70) 2017 Table 300.5
below_2in_concrete450150300150150In trench below 50 mm (2 in.) thick concrete or equivalent300.5NEC (NFPA 70) 2017 Table 300.5
under_4in_exterior_concrete_slab450100100150150Under minimum 102 mm (4 in.) thick concrete exterior slab, no vehicular traffic, slab extends 152 mm beyond installation300.5NEC (NFPA 70) 2017 Table 300.5
under_building00000Under a building (in raceway or Type MC/MI cable)300.5NEC (NFPA 70) 2017 Table 300.5
airport_runway450450450450450In or under airport runways, including adjacent areas where trespassing prohibited300.5NEC (NFPA 70) 2017 Table 300.5

This is a sample. Search the full nec underground cover dataset and 350+ more by creating a free account and accessing the database.