Nec General Lighting Loads: restaurants to warehouses_storage

NEC (NFPA 70) Table 220.12 — general lighting load unit values by occupancy type used for calculating branch circuit, feeder, and service loads in VA per square foot (and VA per square meter)

Electrical Engineeringoccupancy_id: restaurants to warehouses_storage5 rows
occupancy idnec sectionoccupancy typestandardunit load va per ft2 (VA/ft2)unit load va per m2 (VA/m2)
restaurants220.12RestaurantsNEC (NFPA 70) 2017 Table 220.12222
schools220.12SchoolsNEC (NFPA 70) 2017 Table 220.12333
storage_spaces_in_occupancy220.12Storage spaces (within preceding occupancies, not dwelling units)NEC (NFPA 70) 2017 Table 220.120.253
stores220.12StoresNEC (NFPA 70) 2017 Table 220.12333
warehouses_storage220.12Warehouses (storage)NEC (NFPA 70) 2017 Table 220.120.253