Nec General Lighting Loads: hospitals to office_buildings

NEC (NFPA 70) Table 220.12 — general lighting load unit values by occupancy type used for calculating branch circuit, feeder, and service loads in VA per square foot (and VA per square meter)

Electrical Engineeringoccupancy_id: hospitals to office_buildings5 rows
occupancy idfootnotenec sectionoccupancy typestandardunit load va per ft2 (VA/ft2)unit load va per m2 (VA/m2)
hospitals220.12HospitalsNEC (NFPA 70) 2017 Table 220.12222
hotels_motelsRefer to 220.14(J) for dwelling units and 220.14(K) for guest rooms and suites.220.12Hotels and motels, including apartment houses without provision for cooking by tenantsNEC (NFPA 70) 2017 Table 220.12222
industrial_commercial_loft220.12Industrial commercial (loft) buildingsNEC (NFPA 70) 2017 Table 220.12222
lodge_rooms220.12Lodge roomsNEC (NFPA 70) 2017 Table 220.121.517
office_buildingsIn addition to the unit load in this table, a load of 1 VA/ft2 (11 VA/m2) shall be included for general-purpose receptacle outlets where the number of general-purpose receptacle outlets is unknown.220.12Office buildingsNEC (NFPA 70) 2017 Table 220.123.539