Nec Conduit Raceway: PVC_80

NEC Chapter 9 conduit and raceway dimensions — internal diameter, total area, and fill areas for EMT, RMC, IMC, PVC conduit types

Electrical Engineeringconduit_type: PVC_803 rows
conduit typetrade size inarea 1 wire pct53 in2 (in2)area 2 wires pct31 in2 (in2)area over2 wires pct40 in2 (in2)internal diameter in (in)total area in2 (in2)
PVC_8010.3650.2130.2750.9360.688
PVC_801-1/20.9070.530.6841.4761.711
PVC_801-1/40.6560.3830.4951.2551.237