NEC Chapter 9 conduit and raceway dimensions — internal diameter, total area, and fill areas for EMT, RMC, IMC, PVC conduit types
| conduit type | trade size in | area 1 wire pct53 in2 (in2) | area 2 wires pct31 in2 (in2) | area over2 wires pct40 in2 (in2) | internal diameter in (in) | total area in2 (in2) |
|---|---|---|---|---|---|---|
| PVC_80 | 1 | 0.365 | 0.213 | 0.275 | 0.936 | 0.688 |
| PVC_80 | 1-1/2 | 0.907 | 0.53 | 0.684 | 1.476 | 1.711 |
| PVC_80 | 1-1/4 | 0.656 | 0.383 | 0.495 | 1.255 | 1.237 |