Nec Conduit Raceway: EMT

NEC Chapter 9 conduit and raceway dimensions — internal diameter, total area, and fill areas for EMT, RMC, IMC, PVC conduit types

Electrical Engineeringconduit_type: EMT3 rows
conduit typetrade size inarea 1 wire pct53 in2 (in2)area 2 wires pct31 in2 (in2)area over2 wires pct40 in2 (in2)internal diameter in (in)total area in2 (in2)
EMT10.4580.2680.3461.0490.864
EMT1-1/21.0790.6310.8141.612.036
EMT1-1/40.7930.4640.5981.381.496