Nec Cable Ampacity: copper

4/0 AWG to 900 kcmil

NEC (NFPA 70) cable ampacity ratings — allowable current for copper and aluminum conductors at 60/75/90°C insulation ratings in raceways and free air; high-temperature conductor ampacity at 150/200/250°C; ambient temperature correction factors; conductor fill adjustment factors

Electrical Engineeringconductor material: copper10 rowsPage 9 of 9
conductor materialconductor sizeampacity 60C (A)ampacity 75C (A)ampacity 90C (A)nec tablestandard
copper4/0 AWG195230260310.16NEC (NFPA 70) Table 310.16
copper400 kcmil280335380310.16NEC (NFPA 70) Table 310.16
copper500 kcmil320380430310.16NEC (NFPA 70) Table 310.16
copper6 AWG556575310.16NEC (NFPA 70) Table 310.16
copper600 kcmil350420475310.16NEC (NFPA 70) Table 310.16
copper700 kcmil385460520310.16NEC (NFPA 70) Table 310.16
copper750 kcmil400475535310.16NEC (NFPA 70) Table 310.16
copper8 AWG405055310.16NEC (NFPA 70) Table 310.16
copper800 kcmil410490555310.16NEC (NFPA 70) Table 310.16
copper900 kcmil435520585310.16NEC (NFPA 70) Table 310.16