310.17#500 kcmil to 4 AWG

NEC (NFPA 70) cable ampacity ratings — allowable current for copper and aluminum conductors at 60/75/90°C insulation ratings in raceways and free air; high-temperature conductor ampacity at 150/200/250°C; ambient temperature correction factors; conductor fill adjustment factors

Electrical Engineeringconductor material: copper8 rowsPage 8 of 9
conductor materialconductor sizeampacity 60C (A)ampacity 75C (A)ampacity 90C (A)installationnec tablestandard
copper310.17#500 kcmil515620700free air310.17NEC (NFPA 70) Table 310.17
copper310.17#6 AWG8095105free air310.17NEC (NFPA 70) Table 310.17
copper310.17#600 kcmil575690780free air310.17NEC (NFPA 70) Table 310.17
copper310.17#700 kcmil630755855free air310.17NEC (NFPA 70) Table 310.17
copper310.17#750 kcmil655785885free air310.17NEC (NFPA 70) Table 310.17
copper310.17#8 AWG607080free air310.17NEC (NFPA 70) Table 310.17
copper310.17#800 kcmil680815920free air310.17NEC (NFPA 70) Table 310.17
copper310.17#900 kcmil730870985free air310.17NEC (NFPA 70) Table 310.17