conductor materialconductor sizeampacity 60C (A)ampacity 75C (A)ampacity 90C (A)installationnec tablestandard
aluminum310.17#400 kcmil355425480free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#500 kcmil405485545free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#6 AWG607580free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#600 kcmil455540615free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#700 kcmil500595675free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#750 kcmil515620700free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#8 AWG455560free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#800 kcmil535645725free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#900 kcmil580700785free air310.17NEC (NFPA 70) Table 310.17