Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Nec Cable Ampacity: aluminum

310.17#2 AWG to 310.17#4/0 AWG

NEC (NFPA 70) cable ampacity ratings — allowable current for copper and aluminum conductors at 60/75/90°C insulation ratings in raceways and free air; high-temperature conductor ampacity at 150/200/250°C; ambient temperature correction factors; conductor fill adjustment factors

Electrical Engineeringconductor material: aluminum10 rowsPage 6 of 9
conductor materialconductor sizeampacity 60C (A)ampacity 75C (A)ampacity 90C (A)installationnec tablestandard
aluminum310.17#2 AWG110135150free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#2/0 AWG175210235free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#2000 kcmil9601,1501,335free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#250 kcmil265315355free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#3 AWG95115130free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#3/0 AWG200240275free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#300 kcmil290350395free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#350 kcmil330395445free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#4 AWG80100110free air310.17NEC (NFPA 70) Table 310.17
aluminum310.17#4/0 AWG235280315free air310.17NEC (NFPA 70) Table 310.17