Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Nec Cable Ampacity: aluminum

310.15B17#350 kcmil to 310.15B17#8 AWG

NEC (NFPA 70) cable ampacity ratings — allowable current for copper and aluminum conductors at 60/75/90°C insulation ratings in raceways and free air; high-temperature conductor ampacity at 150/200/250°C; ambient temperature correction factors; conductor fill adjustment factors

Electrical Engineeringconductor material: aluminum10 rowsPage 4 of 9
conductor materialconductor sizeampacity 60C (A)ampacity 75C (A)ampacity 90C (A)installationnec tablestandard
aluminum310.15B17#350 kcmil330395445free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#4 AWG80100115free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#4/0 AWG235280315free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#400 kcmil355425480free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#500 kcmil405485545free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#6 AWG607585free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#600 kcmil455545615free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#700 kcmil500595670free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#750 kcmil515620700free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#8 AWG455560free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)

What else is in Engineering Database

Calculators that use this data

Related data