Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Nec Cable Ampacity: aluminum

310.15B17#1250 kcmil to 310.15B17#300 kcmil

NEC (NFPA 70) cable ampacity ratings — allowable current for copper and aluminum conductors at 60/75/90°C insulation ratings in raceways and free air; high-temperature conductor ampacity at 150/200/250°C; ambient temperature correction factors; conductor fill adjustment factors

Electrical Engineeringconductor material: aluminum10 rowsPage 3 of 9
conductor materialconductor sizeampacity 60C (A)ampacity 75C (A)ampacity 90C (A)installationnec tablestandard
aluminum310.15B17#1250 kcmil710855965free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#1500 kcmil7959501,070free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#1750 kcmil8751,0501,185free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#2 AWG110135150free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#2/0 AWG175210235free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#2000 kcmil9601,1501,295free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#250 kcmil265315355free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#3 AWG95115130free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#3/0 AWG200240270free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)
aluminum310.15B17#300 kcmil290350395free air310.15(B)(17)NEC (NFPA 70) 2017 Edition Table 310.15(B)(17)