Nec Box Fill: metal box

FD multiple cover 60.3 depth to FS single cover 44.5 depth

NEC (NFPA 70) box fill requirements — minimum volume for metal outlet/device/junction boxes (Table 314.16(A)) and volume allowance per conductor by wire size (Table 314.16(B))

Electrical Engineeringrecord type: metal box4 rowsPage 3 of 3
record typebox keydescriptionmax conductors awg 10max conductors awg 12max conductors awg 14max conductors awg 16max conductors awg 18max conductors awg 6max conductors awg 8min volume cm3 (cm3)min volume in3 (in3)nec tablestandard
metal boxFD multiple cover 60.3 depthFD min. 60.3 mm depth, multiple cover9101213164839524314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal boxFD single cover 60.3 depthFD min. 60.3 mm depth, single cover78910123629518314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal boxFS multiple cover 44.5 depthFS min. 44.5 mm depth, multiple cover78910123629518314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal boxFS single cover 44.5 depthFS min. 44.5 mm depth, single cover566792422113.5314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16