record typebox keydescriptionmax conductors awg 10max conductors awg 12max conductors awg 14max conductors awg 16max conductors awg 18max conductors awg 6max conductors awg 8min volume cm3 (cm3)min volume in3 (in3)nec tablestandard
metal box120x38 square120 x 38 (4-11/16 x 1-1/2) square11131416195948429.5314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box120x54 square120 x 54 (4-11/16 x 2-1/8) square161821242881468942314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box75x50x38 device75 x 50 x 38 (3 x 2 x 1-1/2) device33345121237.5314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box75x50x50 device75 x 50 x 50 (3 x 2 x 2) device445562316410314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box75x50x57 device75 x 50 x 57 (3 x 2 x 2-1/4) device445672317210.5314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box75x50x65 device75 x 50 x 65 (3 x 2 x 2-1/2) device556782420512.5314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box75x50x70 device75 x 50 x 70 (3 x 2 x 2-3/4) device567892423014314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box75x50x90 device75 x 50 x 90 (3 x 2 x 3-1/2) device78910123629518314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box95x50x65 masonry95 x 50 x 65 (3-3/4 x 2 x 2-1/2) masonry box567892423014314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16
metal box95x50x90 masonry95 x 50 x 90 (3-3/4 x 2 x 3-1/2) masonry box891012144734421314.16(A)NEC (NFPA 70) 2017 Edition Table 314.16