Medium Voltage Cable: 500_KCMIL

Medium-voltage cable ampacity and physical properties for copper XLPE-insulated cables. Covers MV-90 (90C) and MV-105 (105C) rated cables, 5kV through 35kV class, conductor sizes 1/0 AWG through 1000 kcmil. Ampacity in duct/conduit and direct buried per NEC Table 310.60 / Article 311. Includes insulation thickness, overall diameter, weight, and DC resistance.

Electrical Engineeringconductor_size: 500_KCMIL3 rows
conductor sizevoltage class tempampacity direct buried A (A)ampacity duct A (A)conductor materialdc resistance ohm kft (ohm/kft)insulation level pct (%)insulation thickness mils (mils)insulation typenotesoverall diameter in (in)temperature rating C (C)voltage classweight lb kft (lb/kft)
500_KCMIL15KV_105C555480copper0.0268100260XLPEMV-105 15kV1.7210515KV1,680
500_KCMIL15KV_90C515445copper0.0268100260XLPE15kV class1.729015KV1,680
500_KCMIL25KV_90C490420copper0.0268100345XLPE25kV class1.919025KV1,900