Medium Voltage Cable: 1/0_AWG
Medium-voltage cable ampacity and physical properties for copper XLPE-insulated cables. Covers MV-90 (90C) and MV-105 (105C) rated cables, 5kV through 35kV class, conductor sizes 1/0 AWG through 1000 kcmil. Ampacity in duct/conduit and direct buried per NEC Table 310.60 / Article 311. Includes insulation thickness, overall diameter, weight, and DC resistance.
| conductor size | voltage class temp | ampacity direct buried A (A) | ampacity duct A (A) | conductor material | dc resistance ohm kft (ohm/kft) | insulation level pct (%) | insulation thickness mils (mils) | insulation type | notes | overall diameter in (in) | temperature rating C (C) | voltage class | weight lb kft (lb/kft) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1/0_AWG | 15KV_105C | 230 | 200 | copper | 0.1276 | 100 | 260 | XLPE | MV-105 15kV | 1.155 | 105 | 15KV | 535 |
| 1/0_AWG | 15KV_90C | 210 | 185 | copper | 0.1276 | 100 | 260 | XLPE | 15kV 100% insulation level; thicker insulation vs 5kV | 1.155 | 90 | 15KV | 535 |
| 1/0_AWG | 25KV_90C | 200 | 175 | copper | 0.1276 | 100 | 345 | XLPE | 25kV class; min size per NEC typically 1/0 AWG | 1.33 | 90 | 25KV | 625 |