Lightning Protection Substation: 345KV
IEEE 998 lightning shielding parameters for outdoor substations using the rolling sphere / electrogeometric model (EGM). Includes striking distance, rolling sphere radius, shielding mast heights, shield wire heights, and maximum horizontal separation by voltage class and BIL.
| voltage class | bil kV (kV) | max horizontal separation ft (ft) | protection angle deg (degrees) | rolling sphere radius ft (ft) | standard | striking distance ft (ft) | typical mast height above bus ft (ft) | typical shield wire height ft (ft) |
|---|---|---|---|---|---|---|---|---|
| 345KV | 1,300 | 120 | 45 | 198 | IEEE 998-2012 | 198 | 95 | 120 |