Lightning Protection Substation: 138KV

IEEE 998 lightning shielding parameters for outdoor substations using the rolling sphere / electrogeometric model (EGM). Includes striking distance, rolling sphere radius, shielding mast heights, shield wire heights, and maximum horizontal separation by voltage class and BIL.

Electrical Engineeringvoltage class: 138KV1 row
voltage classbil kV (kV)max horizontal separation ft (ft)protection angle deg (degrees)rolling sphere radius ft (ft)standardstriking distance ft (ft)typical mast height above bus ft (ft)typical shield wire height ft (ft)
138KV6507545120IEEE 998-20121206075