Lightning Protection Substation: 15KV to 115KV

IEEE 998 lightning shielding parameters for outdoor substations using the rolling sphere / electrogeometric model (EGM). Includes striking distance, rolling sphere radius, shielding mast heights, shield wire heights, and maximum horizontal separation by voltage class and BIL.

Electrical Engineeringvoltage_class: 15KV to 115KV4 rows
voltage classbil kV (kV)max horizontal separation ft (ft)protection angle deg (degrees)rolling sphere radius ft (ft)standardstriking distance ft (ft)typical mast height above bus ft (ft)typical shield wire height ft (ft)
25KV150304548IEEE 998-2012482530
38KV200354557IEEE 998-2012573035
69KV350504580IEEE 998-2012804050
115KV5506545106IEEE 998-20121065565