Lightning Protection Substation: 138KV to 500KV

IEEE 998 lightning shielding parameters for outdoor substations using the rolling sphere / electrogeometric model (EGM). Includes striking distance, rolling sphere radius, shielding mast heights, shield wire heights, and maximum horizontal separation by voltage class and BIL.

Electrical Engineeringvoltage_class: 138KV to 500KV3 rows
voltage classbil kV (kV)max horizontal separation ft (ft)protection angle deg (degrees)rolling sphere radius ft (ft)standardstriking distance ft (ft)typical mast height above bus ft (ft)typical shield wire height ft (ft)
138KV6507545120IEEE 998-20121206075
161KV7508045133IEEE 998-20121336580
230KV9009545152IEEE 998-20121527595

This is a sample. Search the full lightning protection substation dataset and 300+ more by creating a free account and accessing the database.