Heat Pump Performance: ground_source_cooling

Heat pump COP and capacity fraction data as a function of outdoor temperature (air-source) or entering water temperature (ground/water-source) — covers air-source heating/cooling, cold-climate ASHP, ground-source, and water-source heat pumps

Mechanical Engineeringheat_pump_type: ground_source_cooling3 rows
heat pump typeoutdoor temp Fcapacity fraction (dimensionless)cop (dimensionless)notespower input kW (kW)
ground_source_cooling501.17.5Ground-source cooling; EWT 50F; ideal loop condition in heating-dominated climate; excellent cooling COP; ClimateMaster TZ30 or WaterFurnace 7-Series achieves EER 40+ at these conditions2.58
ground_source_cooling601.056.8Ground-source cooling; EWT 60F; good loop condition; well-designed loop field maintains 45-65F EWT year-round; COP significantly better than air-cooled at 95F ambient2.72
ground_source_cooling701.026Ground-source cooling; EWT 70F; moderate loop temperature; typical mid-summer EWT for adequately sized loop; still substantially better than air-cooled chiller at 95F ambient2.99