Heat Pump Performance: ground_source

Heat pump COP and capacity fraction data as a function of outdoor temperature (air-source) or entering water temperature (ground/water-source) — covers air-source heating/cooling, cold-climate ASHP, ground-source, and water-source heat pumps

Mechanical Engineeringheat_pump_type: ground_source3 rows
heat pump typeoutdoor temp Fcapacity fraction (dimensionless)cop (dimensionless)notespower input kW (kW)
ground_source200.652.6Ground-source heating; EWT 20F; requires anti-freeze in loop (propylene glycol 30%+); marginal loop condition indicating thermal depletion; COP drops significantly; loop upsizing recommended4.4
ground_source300.783.2EWT 30F; marginal loop condition; anti-freeze (propylene glycol 20%) required below 32F EWT4.29
ground_source400.93.8EWT 40F; colder loop reduces COP; typical late-winter condition in northern climates4.16