Harmonic Distortion Limits: <20

IEEE 519-2022 harmonic distortion limits at the Point of Common Coupling (PCC). Current distortion limits by ISC/IL ratio and individual harmonic group; voltage distortion limits by bus voltage level. Covers systems from <=1kV through >161kV.

Electrical Engineeringisc_il_ratio: <203 rows
isc il ratiovoltage class kvh 11 to 16 pct (%)h 17 to 22 pct (%)h 23 to 34 pct (%)h 2 to 10 pct (%)h 35 to 50 pct (%)notestdd pct (%)voltage individual pct (%)voltage thd pct (%)
<20EHV_GT161KV21.50.640.3V > 161kV; transmission; THD may reach 2.0% for HVDC terminal effects511.5
<20HV_69_161KV21.50.640.369kV < V ≤ 161kV; subtransmission51.52.5
<20LV_1KV21.50.640.3Systems ≤1.0kV; even harmonics ≤6th limited to 50% of stated values558

This is a sample. Search the full harmonic distortion limits dataset and 300+ more by creating a free account and accessing the database.