IEEE 519-2022 harmonic distortion limits at the Point of Common Coupling (PCC). Current distortion limits by ISC/IL ratio and individual harmonic group; voltage distortion limits by bus voltage level. Covers systems from <=1kV through >161kV.

Electrical Engineeringisc_il_ratio: >10003 rows
isc il ratiovoltage class kvh 11 to 16 pct (%)h 17 to 22 pct (%)h 23 to 34 pct (%)h 2 to 10 pct (%)h 35 to 50 pct (%)notestdd pct (%)voltage individual pct (%)voltage thd pct (%)
>1000EHV_GT161KV762.5151.4V > 161kV; transmission2011.5
>1000HV_69_161KV762.5151.469kV < V ≤ 161kV201.52.5
>1000LV_1KV762.5151.4Systems ≤1.0kV; dedicated feeder2058