IEEE 80 grounding grid design parameters including touch/step voltage safety limits (50 and 70 kg body weight), decrement factors by X/R ratio, and typical soil resistivity values by soil type.

Electrical Engineeringparameter_type: TOUCH_VOLTAGE_LIMIT3 rows
parameter typeconditionbody weight kg (kg)decrement factor (dimensionless)limiting valuenotesunit
TOUCH_VOLTAGE_LIMIT50KG_BODY_0.1S501116ts=0.1s fault clearing; Vs_touch=1000*(Ib*Zth) approxV
TOUCH_VOLTAGE_LIMIT50KG_BODY_0.25S50177.9ts=0.25sV
TOUCH_VOLTAGE_LIMIT50KG_BODY_0.5S50162.5ts=0.5sV