Grounding Grid Design: DECREMENT_FACTOR

IEEE 80 grounding grid design parameters including touch/step voltage safety limits (50 and 70 kg body weight), decrement factors by X/R ratio, and typical soil resistivity values by soil type.

Electrical Engineeringparameter_type: DECREMENT_FACTOR3 rows
parameter typeconditionlimiting valuenotesunit
DECREMENT_FACTORFAULT_DUR_0.08S_X_R_101.65X/R=10; Df per IEEE 80 Table 13.1dimensionless
DECREMENT_FACTORFAULT_DUR_0.1S_X_R_101.58X/R=10dimensionless
DECREMENT_FACTORFAULT_DUR_0.1S_X_R_201.76X/R=20dimensionless

This is a sample. Search the full grounding grid design dataset and 300+ more by creating a free account and accessing the database.