Fuse Characteristics: IEC_gM

Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class. Covers UL 248 classes (J, RK1, RK5, CC, T, L, G, H, K) and IEC 60269 types (gG, gM, aR, aM). Includes melting and clearing I2t let-through energy ranges, peak let-through current, conventional fusing/non-fusing current factors, rejection feature type, and application guidance.

Electrical Engineeringfuse_class: IEC_gM1 row
fuse classrecord idamp rating max (A)amp rating min (A)applicationconventional fusing current factor (dimensionless)conventional nonfusing current factor (dimensionless)current limitingdimensions ferrule bladefuse typeinterrupting rating kA ac (kA)notesrejection featuretime delayul standardvoltage rating V (V)
IEC_gMgm_500v1606IEC gM 500VAC 6-160A; motor duty dual marking (e.g. gM 63M80: 63A motor start limit 80A cable protection); single element with two distinct operating zones; used to protect both motor windings and supply cable21.35current_limitingknife_blade_NHgM120gM fuse dual rating: first number is rated current (cable protection) second number (higher) is motor protection threshold; breaks short circuits up to 120kA; IEC 60269-4 covers motor circuit applications; aM often preferred for simplicitynonedual_purposeIEC_60269-2500

This is a sample. Search the full fuse characteristics dataset and 300+ more by creating a free account and accessing the database.