Explore the Engineering Database more efficiently by signing up for free. Sign up free
RK5-600v-Td — Class RK5
- Fuse Class
- Class RK5
- Record Id
- RK5 600v Td
- Amp Rating Max (A)
- 600
- Amp Rating Min (A)
- 0.1
- Application
- Time-Delay Class RK5; Dual element; 10s at 500%; Very Common for Motor protection; NEC 430.52 Allows 175% Max for Td fuses; Lower Cost vs RK1 Acceptable in Many Applications
- Conventional Fusing Current Factor (dimensionless)
- 1.35
- Conventional Nonfusing Current Factor (dimensionless)
- 1.1
- Current Limiting
- Current Limiting
- Dimensions Ferrule Blade
- Class R Ferrule Or Blade
- Fuse Type
- RK5 Time Delay
- Interrupting Rating kA AC (kA)
- 200
- Interrupting Rating kA DC (kA)
- 20
- Rejection Feature
- Rejection Notch Class R Blade
- Standard
- Ul 248-12
- Time Delay
- Time Delay
- Voltage Rating V (V)
- 600
Source: UL_248-12