Explore the Engineering Database more efficiently by signing up for free. Sign up free

RK5-600v — Class RK5

Fuse Class
Class RK5
Record Id
RK5 600v
Amp Rating Max (A)
600
Amp Rating Min (A)
0.1
Application
Class RK5 600VAC; One-Time Or Renewable design; Provides Current Limitation and Rejection feature; Lower Peak Arc-Flash Energy Than H Or K fuses; Common Upgrade From Class H Installations
Conventional Fusing Current Factor (dimensionless)
1.1
Conventional Nonfusing Current Factor (dimensionless)
0.9
Current Limiting
Current Limiting
Dimensions Ferrule Blade
Class R Ferrule Or Blade
Fuse Type
RK5
Interrupting Rating kA AC (kA)
200
Interrupting Rating kA DC (kA)
20
Rejection Feature
Rejection Notch Class R Blade
Standard
Ul 248-12
Time Delay
Fast Acting
Voltage Rating V (V)
600

Source: UL_248-12

CLASS_RK5 — record id rk5_600v · amp rating min 0.1 A | Fuse Characteristics | Engineering Database