Explore the Engineering Database more efficiently by signing up for free. Sign up free

L-Lt-401-600 — Class L

Fuse Class
Class L
Record Id
L Lt 401 600
Amp Rating Label
401-600
Amp Rating Max (A)
600
Amp Rating Min (A)
401
I2T 100kA A2s (A2s)
2,500,000
I2T 200kA A2s (A2s)
2,500,000
I2T 300kA A2s (A2s)
3,000,000
I2T 50kA A2s (A2s)
2,500,000
Peak Lt 100kA a (A)
45,000
Peak Lt 200kA a (A)
70,000
Peak Lt 300kA a (A)
101,367
Peak Lt 50kA a (A)
35,000
Peak Lt Function
Y = 3E-07X2 + 0.15X + 26667
Standard
IEEE Std 3004.3-2020
Voltage Rating V (V)
600

Source: IEEE Std 3004.3-2020

CLASS_L — record id l_lt_401_600 · amp rating label 401-600 · i2t 200kA A2s 2500000 A2s · i2t 300kA A2s 3000000 A2s · peak lt 200kA A 70000 A | Fuse Characteristics | Engineering Database