H17-100 — Direct Fired Furnace

Equipment Type
Direct Fired Furnace
Class Code
H17-100
Description
Direct Fired furnace, ≤ 500
Failure Rate per Year (failures/year)
0.037173
Failures (count)
6
Mdt Hours (h)
3.82
Mtbf Hours (h)
235,652
Mttm Hours (h)
3.33
Mttr Hours (h)
0.83
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
161.4

Source: IEEE Std 3006.8-2018 Table 2