E06-113 — Cable
- Equipment Type
- Cable
- Class Code
- E06-113
- Description
- Cable, ac, 0 V to 600 V, Above
- Failure Rate per Year (failures/year)
- 0.00012
- Failures (count)
- 4
- Mdt Hours (h)
- 0.08
- Mtbf Hours (h)
- 72,896,904
- Mttm Hours (h)
- 0.05
- Mttr Hours (h)
- 2.5
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 33,286.3