Explore the Engineering Database more efficiently by signing up for free. Sign up free

H08-220 — Boiler

Equipment Type
Boiler
Class Code
H08-220
Description
Boiler, steam, Low pressure, ≤
Failure Rate per Year (failures/year)
0.446098
Failures (count)
721
Mdt Hours (h)
40.86
Mtbf Hours (h)
19,637
Mttm Hours (h)
48.03
Mttr Hours (h)
13.25
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
1,616.2

Source: IEEE Std 3006.8-2018 Table 2

Boiler — class code H08-220 · description Boiler, steam, low pressure, ≤ · failure rate per year 0.446098 failures/year · unit years 1616.2 unit-years · mtbf hours 19637 h | Equipment Failure Rates | Engineering Database