H08-220 — Boiler
- Equipment Type
- Boiler
- Class Code
- H08-220
- Description
- Boiler, steam, Low pressure, ≤
- Failure Rate per Year (failures/year)
- 0.446098
- Failures (count)
- 721
- Mdt Hours (h)
- 40.86
- Mtbf Hours (h)
- 19,637
- Mttm Hours (h)
- 48.03
- Mttr Hours (h)
- 13.25
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 1,616.2
Source: IEEE Std 3006.8-2018 Table 2