Duct Construction Specs: system leakage

High pressure induction operating to VAV CAV return upstream box construction

ASHRAE duct construction specifications: sheet metal gauge thickness and weight for galvanized, uncoated, and stainless steel ductwork; duct leakage percentages by leakage class and flow ratio; and maximum allowable fan system leakage by HVAC system type

Mechanical Engineeringdata type: system leakage10 rowsPage 2 of 3
data typegagemax leakage pct (%)system typetest conditiontest pressure inwg (inWG)
system leakageHigh pressure induction operating5High-pressure induction systemsOperating
system leakageMultizone supply construction5Multizone supply, return, or exhaust systemsDuring construction2
system leakageMultizone supply operating5Multizone supply, return, or exhaust systemsOperating
system leakageSingle zone supply construction5Single-zone supply, return, or exhaust systemsDuring construction2
system leakageSingle zone supply operating5Single-zone supply, return, or exhaust systemsOperating
system leakageSupply return outdoors construction2Supply and return ductwork located outdoorsDuring construction3
system leakageSupply return outdoors operating2Supply and return ductwork located outdoorsOperating
system leakageVAV CAV return downstream box construction5VAV or CAV return systemsDuring construction3
system leakageVAV CAV return operating5VAV or CAV return systemsOperating
system leakageVAV CAV return upstream box construction5VAV or CAV return systemsDuring construction1

What else is in Engineering Database