District Energy Systems: flowmeter_types

District energy systems design reference data — chiller technology COP ranges, pipe insulation thermal properties and moisture performance, soil thermal conductivity, buried pre-insulated pipe heat loss, piping material comparisons, direct vs. indirect interconnection trade-offs, heating system conversion suitability, and district energy flow meter types per ASHRAE Handbook HVAC Systems and Equipment 2020 Chapter 12

Mechanical Engineeringcategory: flowmeter_types3 rows
categoryitem keydescriptionvalue text
flowmeter_typesElectromagneticElectromagnetic flowmeter for district energy meteringAccuracy ±0.15% to 1% rate; turndown 30:1 to 100:1
flowmeter_typesOrifice_PlateOrifice plate flowmeter for district energy meteringAccuracy ±1% to 5% full scale; turndown 3:1 to 5:1
flowmeter_typesTurbineTurbine flowmeter for district energy meteringAccuracy ±0.15% to 0.5% rate; turndown 10:1 to 50:1