District energy systems design reference data — chiller technology COP ranges, pipe insulation thermal properties and moisture performance, soil thermal conductivity, buried pre-insulated pipe heat loss, piping material comparisons, direct vs. indirect interconnection trade-offs, heating system conversion suitability, and district energy flow meter types per ASHRAE Handbook HVAC Systems and Equipment 2020 Chapter 12

Mechanical Engineeringcategory: buried_pipe_thermal3 rows
categoryitem keydescriptionunitvalue minvalue text
buried_pipe_thermalPipe_OD_1p5in_k0p20_10ftBuried district heating pipe: OD 1.5 in mineral wool 1 in urethane foam 1 in air space 1 in depth 10 ft soil k=0.20Btu/h-ft53.4Heat loss 53.4 Btu/h-ft
buried_pipe_thermalPipe_OD_2in_k0p80_10ftBuried district heating pipe: OD 2 in mineral wool 1 in urethane foam 1 in air space 1 in depth 10 ft soil k=0.80Btu/h-ft72Heat loss 72.0 Btu/h-ft
buried_pipe_thermalPipe_OD_2in_k0p80_5ftBuried district heating pipe: OD 2 in mineral wool 1 in urethane foam 1 in air space 1 in depth 5 ft soil k=0.80Btu/h-ft73.9Heat loss 73.9 Btu/h-ft