load categoryload idconcentrated kN (kN)concentrated lbs (lbs)namereduciblestandardsubcategoryuniform kPa (kPa)uniform psf (psf)
FLOOR LIVEhospital corridors first4.4481,000Hospitals — first-floor corridorsnoASCE 7-22 Table 4.3-1hospital4.788100
FLOOR LIVEhospital operating rooms4.4481,000Hospitals — operating rooms and laboratoriesyesASCE 7-22 Table 4.3-1hospital2.87360
FLOOR LIVEhospital patient rooms4.4481,000Hospitals — patient roomsyesASCE 7-22 Table 4.3-1hospital1.91540
FLOOR LIVEhotel corridorsHotels — corridors above first flooryesASCE 7-22 Table 4.3-1hotel3.8380
FLOOR LIVEhotel guest roomsHotels — guest rooms and private corridorsyesASCE 7-22 Table 4.3-1hotel1.91540
FLOOR LIVEhotel public roomsHotels — public roomsnoASCE 7-22 Table 4.3-1hotel4.788100
FLOOR LIVEjail cell blocksJail — cell blocksyesIBC 2024 Table 1607.1institutional1.91540
FLOOR LIVEjail corridorsJail — corridorsnoIBC 2024 Table 1607.1institutional4.788100
FLOOR LIVElaundry residentialLaundry — residentialyesASCE 7-22 Table 4.3-1residential1.91540
FLOOR LIVElibrary corridors4.4481,000Libraries — corridors above first flooryesASCE 7-22 Table 4.3-1library3.8380