Datacenter Cooling Specs: Vertiv Liebert DS 077 WC upflow FW
cooling capacity 75F DB EWT83F to cooling capacity 85F DB EWT83F
Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.
| manufacturer model | spec type | airflow direction | compressor type | cooling type | entering air temp c (degC) | entering water temp c (degC) | leaving water temp c (degC) | manufacturer | model series | sensible cooling capacity kw (kW) | total cooling capacity kw (kW) | water flow rate lpm (L/min) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Vertiv Liebert DS 077 WC upflow FW | cooling capacity 75F DB EWT83F | upflow | semi hermetic | water cooled | 23.9 | 28.3 | 35 | Vertiv | Liebert DS | 65.6 | 78 | 225 |
| Vertiv Liebert DS 077 WC upflow FW | cooling capacity 80F DB EWT83F | upflow | semi hermetic | water cooled | 26.7 | 28.3 | 35 | Vertiv | Liebert DS | 76.2 | 82.7 | 235.1 |
| Vertiv Liebert DS 077 WC upflow FW | cooling capacity 85F DB EWT83F | upflow | semi hermetic | water cooled | 29.4 | 28.3 | 35 | Vertiv | Liebert DS | 83.9 | 86.6 | 243.1 |