Datacenter Cooling Specs: Schneider InRow RC 300mm ACRC100
cooling capacity 100F DB to physical
Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.
| manufacturer model | spec type | airflow direction | cooling type | depth mm (mm) | entering air temp c (degC) | frequency hz | height mm (mm) | manufacturer | model series | phase (dimensionless) | power input kw (kW) | sensible cooling capacity kw (kW) | total cooling capacity kw (kW) | voltage v (V) | weight kg (kg) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Schneider InRow RC 300mm ACRC100 | cooling capacity 100F DB | back to front | chilled water | — | 37.8 | — | — | Schneider Electric | InRow RC | — | 1.1 | 28.7 | 28.7 | — | — |
| Schneider InRow RC 300mm ACRC100 | cooling capacity 105F DB | back to front | chilled water | — | 40.6 | — | — | Schneider Electric | InRow RC | — | 1.1 | 30.7 | 30.7 | — | — |
| Schneider InRow RC 300mm ACRC100 | cooling capacity 80F DB | back to front | chilled water | — | 26.7 | — | — | Schneider Electric | InRow RC | — | 1.1 | 13.2 | 13.2 | — | — |
| Schneider InRow RC 300mm ACRC100 | cooling capacity 85F DB | back to front | chilled water | — | 29.4 | — | — | Schneider Electric | InRow RC | — | 1.1 | 18.2 | 18.2 | — | — |
| Schneider InRow RC 300mm ACRC100 | cooling capacity 90F DB | back to front | chilled water | — | 32.2 | — | — | Schneider Electric | InRow RC | — | 1.1 | 21.7 | 21.7 | — | — |
| Schneider InRow RC 300mm ACRC100 | cooling capacity 95F DB | back to front | chilled water | — | 35 | — | — | Schneider Electric | InRow RC | — | 1.1 | 25.2 | 25.2 | — | — |
| Schneider InRow RC 300mm ACRC100 | electrical | back to front | chilled water | — | — | 50/60 | — | Schneider Electric | InRow RC | 1 | — | — | — | 100 | — |
| Schneider InRow RC 300mm ACRC100 | physical | back to front | chilled water | 300 | — | — | 900 | Schneider Electric | InRow RC | — | — | — | — | — | 2,000 |