Datacenter Cooling Specs: Vertiv Liebert DS 077 WC downflow FW

cooling capacity 75F DB EWT83F to cooling capacity 85F DB EWT83F

Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.

Mechanical Engineeringmanufacturer model: Vertiv Liebert DS 077 WC downflow FW3 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)entering water temp c (degC)leaving water temp c (degC)manufacturermodel seriessensible cooling capacity kw (kW)total cooling capacity kw (kW)water flow rate lpm (L/min)
Vertiv Liebert DS 077 WC downflow FWcooling capacity 75F DB EWT83Fdownflowsemi hermeticwater cooled23.928.335VertivLiebert DS68.279.4226.7
Vertiv Liebert DS 077 WC downflow FWcooling capacity 80F DB EWT83Fdownflowsemi hermeticwater cooled26.728.335VertivLiebert DS76.783234.9
Vertiv Liebert DS 077 WC downflow FWcooling capacity 85F DB EWT83Fdownflowsemi hermeticwater cooled29.428.335VertivLiebert DS84.386.9243.2