Home/Reference Data/Datacenter Cooling Specs/Vertiv Liebert DS 077 Glycol downflow

Datacenter Cooling Specs: Vertiv Liebert DS 077 Glycol downflow

cooling capacity 75F DB EWT104F to cooling capacity 85F DB EWT104F

Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.

Mechanical Engineeringmanufacturer model: Vertiv Liebert DS 077 Glycol downflow3 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)entering water temp c (degC)leaving water temp c (degC)manufacturermodel seriessensible cooling capacity kw (kW)total cooling capacity kw (kW)water flow rate lpm (L/min)
Vertiv Liebert DS 077 Glycol downflowcooling capacity 75F DB EWT104Fdownflowsemi hermeticglycol cooled23.94046.1VertivLiebert DS63.569.7251.4
Vertiv Liebert DS 077 Glycol downflowcooling capacity 80F DB EWT104Fdownflowsemi hermeticglycol cooled26.74046.1VertivLiebert DS71.173.3261.5
Vertiv Liebert DS 077 Glycol downflowcooling capacity 85F DB EWT104Fdownflowsemi hermeticglycol cooled29.44046.1VertivLiebert DS77.577.7273.1