Mechanical Engineeringmanufacturer model: Vertiv Liebert DS 077 DX upflow3 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)manufacturermodel seriesmop a (A)sensible cooling capacity kw (kW)total cooling capacity kw (kW)
Vertiv Liebert DS 077 DX upflowcooling capacity 75F DB ACupflowsemi hermeticDX air cooled23.9VertivLiebert DSR407C62.873.3
Vertiv Liebert DS 077 DX upflowcooling capacity 80F DB ACupflowsemi hermeticDX air cooled26.7VertivLiebert DSR407C72.977.5
Vertiv Liebert DS 077 DX upflowcooling capacity 85F DB ACupflowsemi hermeticDX air cooled29.4VertivLiebert DSR407C79.881.2