Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free
Home/Reference Data/Datacenter Cooling Specs/Vertiv Liebert DS 042 WC downflow FW

Datacenter Cooling Specs: Vertiv Liebert DS 042 WC downflow FW

cooling capacity 75F DB EWT83F to cooling capacity 85F DB EWT83F

Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.

Mechanical Engineeringmanufacturer model: Vertiv Liebert DS 042 WC downflow FW3 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)entering water temp c (degC)leaving water temp c (degC)manufacturermodel seriessensible cooling capacity kw (kW)total cooling capacity kw (kW)water flow rate lpm (L/min)
Vertiv Liebert DS 042 WC downflow FWcooling capacity 75F DB EWT83Fdownflowdigital scrollwater cooled23.928.335VertivLiebert DS38.943121.8
Vertiv Liebert DS 042 WC downflow FWcooling capacity 80F DB EWT83Fdownflowdigital scrollwater cooled26.728.335VertivLiebert DS43.745.1126.9
Vertiv Liebert DS 042 WC downflow FWcooling capacity 85F DB EWT83Fdownflowdigital scrollwater cooled29.428.335VertivLiebert DS47.547.6132.5

What else is in Engineering Database

Calculators that use this data

Related data