Datacenter Cooling Specs: Vertiv Liebert DS 035 Glycol downflow

cooling capacity 75F DB EWT104F to physical

Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.

Mechanical Engineeringmanufacturer model: Vertiv Liebert DS 035 Glycol downflow4 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)entering water temp c (degC)leaving water temp c (degC)manufacturermodel seriessensible cooling capacity kw (kW)total cooling capacity kw (kW)water flow rate lpm (L/min)
Vertiv Liebert DS 035 Glycol downflowcooling capacity 75F DB EWT104Fdownflowdigital scrollglycol cooled23.94046.1VertivLiebert DS31.733.1121.2
Vertiv Liebert DS 035 Glycol downflowcooling capacity 80F DB EWT104Fdownflowdigital scrollglycol cooled26.74046.1VertivLiebert DS35.135.1126.8
Vertiv Liebert DS 035 Glycol downflowcooling capacity 85F DB EWT104Fdownflowdigital scrollglycol cooled29.44046.1VertivLiebert DS37.537.5133.2
Vertiv Liebert DS 035 Glycol downflowphysicaldownflowdigital scrollglycol cooledVertivLiebert DS