Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free
Home/Reference Data/Datacenter Cooling Specs/Vertiv Liebert DS 035 DX upflow

Datacenter Cooling Specs: Vertiv Liebert DS 035 DX upflow

cooling capacity 75F DB AC to cooling capacity 85F DB AC

Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.

Mechanical Engineeringmanufacturer model: Vertiv Liebert DS 035 DX upflow3 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)manufacturermodel seriesmop a (A)sensible cooling capacity kw (kW)total cooling capacity kw (kW)
Vertiv Liebert DS 035 DX upflowcooling capacity 75F DB ACupflowdigital scrollDX air cooled23.9VertivLiebert DSR407C29.933.8
Vertiv Liebert DS 035 DX upflowcooling capacity 80F DB ACupflowdigital scrollDX air cooled26.7VertivLiebert DSR407C34.235.8
Vertiv Liebert DS 035 DX upflowcooling capacity 85F DB ACupflowdigital scrollDX air cooled29.4VertivLiebert DSR407C37.437.6

What else is in Engineering Database

Calculators that use this data

Related data