Explore the Engineering Database more efficiently by signing up for free. Sign up free

6300A-Copper-IEC-En-61439-6 — Schneider I-Line II

Manufacturer Series
Schneider I-Line II
Rating Config
6300A Copper IEC/EN 61439-6
Ampere Rating a (A)
6,300
Conductor Material
Copper
Housing Width MM (mm)
638
Impedance Mohm per M (mΩ/m)
0.01
IP Rating
IP54
Manufacturer
Schneider
Phases
3
Reactance Mohm per M (mΩ/m)
0.005
Resistance Mohm per M (mΩ/m)
0.009
Short Circuit Duration
1-Second Rms Sym
Short Circuit Rating Ka (kA)
120
Standard
IEC/EN 61439-6
Vd PF100 V per M (V/m)
0.098
Voltage Rating V
1000
Weight 3w Kg per M (kg/m)
108.9
Weight 4w 100N Kg per M (kg/m)
134.8
Weight 4w 200N Kg per M (kg/m)
146.7

Source: IEC/EN 61439-6

Schneider_I-Line_II — rating config 6300A_copper_IEC/EN 61439-6 · reactance mohm per m 0.005 mΩ/m · resistance mohm per m 0.009 mΩ/m · vd pf100 v per m 0.098 V/m · ampere rating a 6300 A | Busway Specs | Engineering Database