Ashrae Ventilation Rates: auditorium to computer_lab

ASHRAE 62.1-2022 minimum outdoor air ventilation rates by occupancy category — per-person rate (Rp, cfm/person) and per-area rate (Ra, cfm/ft2) for the Ventilation Rate Procedure

Mechanical Engineeringoccupancy_category: auditorium to computer_lab5 rows
occupancy categorydefault occupant density per 1000ft2 (people/1000ft2)descriptionnotesra cfm ft2 (cfm/ft2)rp cfm person (cfm/person)
auditorium150Theaters auditoriums performing artsApplies to main seating bowl0.065
bar_lounge100Bars cocktail lounges and entertainment venuesHigher density; includes smoking-equivalent allowance0.187.5
beauty_salon25Beauty salons nail salons and spasChemical vapors from solvents and adhesives0.1220
classroom_k1235K-12 classrooms and lecture hallsPrimary and secondary school classrooms0.1210
computer_lab25Computer labs and data processing roomsModerate occupancy and thermal loads0.065