Vibration Isolation Mounts: rubber_pad

Vibration isolation mount specifications covering 8 mount types (rubber pad, neoprene pad, cork pad, elastomeric sandwich, steel spring, wire rope, air spring, inertia base) across light/medium/heavy/extra-heavy load ranges — natural frequency, static deflection, damping ratio, isolation efficiency, temperature limits, and dynamic stiffness

Civil Engineeringmount_type: rubber_pad3 rows
mount typerecord iddamping ratio (dimensionless)durometer Shore A (Shore_A)dynamic stiffness lb per in (lb/in)isolation efficiency pct at ratio 3 (%)load capacity lb (lb)load rangematerialnatural frequency Hz (Hz)static deflection in (in)temperature range max F (degF)temperature range min F (degF)typical applications
rubber_padheavy#neoprene0.08709,375861,500heavyneoprene7.80.16200-20Large HVAC, mid-size compressors
rubber_padheavy#neoprene#90.087018,750863,000heavyneoprene7.80.16200-20Large compressors, generators
rubber_padlight#natural_rubber0.05401568725lightnatural_rubber7.80.16180-40Small pumps, fans, residential HVAC